Application: designed to use for isolation, conversion of  NAMUR, contact signals to NPN or relays outputs
Number of channels: 1 or 2
Mounting:  Power rail / DIN rail (35mm)
Functions:  interface for NAMUR sensors and switches
extended self diagnostics and detection of cable fault
SIL2 certified
programmed with detachable displays 45XX
Input:  NAMUR / mechanical contact (0 ÷ 5kHz; 0.1ms)
Output:  Relay: 20Hz, 250VAC/30VDC/2A
NPN: 
5kHz, >0.1ms
Status relay: 110VDC/125VAC, 0.3ADC/0.5AAC
Supply voltage:  19.2 ÷ 31.2VDC
Auxiliary NAMUR supplies:  8 VDC / 8mA
Isolation voltage:  2.6 kVAC
Programming:  4501/4511 displays
Ambient temperature:  -20 ÷ 60ºC
Protection class: 

IP20

Dimensions (H x W x D): 

109 x 23.5 x 104 mm

Weight: 

170gr 

Approvals:

ATEX (zone 2), DNV, SIL2